===================================================================== = CPS-MCS341 Series Firmware Upgrade = = CPS-MCS341 Series firmware Ver3.10.2 = = CONTEC Co.,Ltd. = ===================================================================== Ÿ Table of Contents ======= Introduction Before upgrading Version upgrading procedure Version upgrading history Ÿ Introduction =========== Thank you for your continued patronage of CONTEC products. This describes the additional information of CPS-MCS341 series firmware upgrade. For how to use the product, please visit our website and see the system setup guide. (http://www.contec.com) Ÿ Firmware upgrading precaution =========== *Do not downgrade the firmware. *The required time for upgrading CPS-MCS341-DS1-131: about 15 minutes other models: about 40 minutes *********************************************************************** * Do not turn off the power when LED ST1 and ST2 are on. * * Doing so may break the data and device will be unable to boot. * *********************************************************************** *Task programs in a former version (1.0.2 and older) will be converted in a Ver.2.0.0 and later versions. However, pages created by the former versions (1.0.2 and older) cannot be used. The screen needs to be created again with new tools. * If the current firmware is less than Ver.3.9.0, please execute the update after updating to Ver.3.9.0. * If the firmware for the CPS-PAV-AES1 series is less than Ver. 1.5.0, version 3.8.0 or later upgrade files cannot be used. Please make sure to confirm that the firmware for the CPS-PAV-AES1 series is Ver. 1.5.0 or higher before updating. Ÿ Before upgrading =========== Have the followings ready EProduct (CPS-MCS341 series) EHost computer ELAN cable EFirmware upgrade file Ÿ Version upgrading procedure =========== 1.Turn on the power of the CPS-MCS341 product. 2.Connect the product to a host computer with a LAN cable. 3.Access the product via web browser from the computer. If the CPS-MCS341 still has the default setting, set the host computer on the same network (e.g.:10.1.1.102) and enter "http://10.1.1.101" in URL. If you are uncertain of your IP address, the default settings (10.1.1.101) can be restored temporarily by turning on the power with SW1-2 switch on. 4.Log in the product. You will be asked to enter a user name and a password. Enter them and click "OK" button. 5.Follow the instruction below to go to "Firmware version up" menu. -The curent firmware version v2.XX In the "Status nemu", click "Maintenace menu", and then "Firmware version up"in the Backup group. Click "Browse" button. Specifiy the file in the host computer to upload. Click "upload" button. -The curent firmware version v3.XX In the "Memu", click "Firmware Version Up" in the Maintenace group. Click "Browse" button. Specifiy the file in the host computer to upload. Click "Update" button. *If the firmware upgrade file is compressed (extension:zip), decompress it before uploadingiextension:spk). 6.Upgrading will start and the product will be rebooted. 7.After rebooting completes, check the version. Access the product via web browser again. From "Menu", click "System" under the group of Status. Ÿ Version upgrading history =========== Ver3.10.2 -------------------------------- Problem Fix - HMI was updated (ver2.18.2 to ver2.18.3). For details, refer to "Online Help". - VTC was updated (ver1.86 to ver1.88). For details, refer to gOnline Helph. Ver3.10.1 -------------------------------- Problem Fix - MQTT certificate information may not be restored successfully. - The FacilityView Transfer Settings screen bug-fixed as follows: Cannot overwrite and save a comment-entered setting when the Cloud Key is set to the maximum limit. When overwriting a Cloud Key that has already been commented and saved, the confirmation message for overwriting is not displayed. - HMI was updated (ver2.18.1 to ver2.18.2). For details, refer to "Online Help". Ver3.10.0 -------------------------------- - WEB server function update. WEB server certificate (self-signed), updated trusted root CA certificate bundle. Added WEB server certificate (self-signed) issuing function. Added function for users to upload any trusted root certificate. Added setting items for communication methods allowed by the web server. HTTP, HTTPS, HTTP/HTTPS (default) - WEB server reinforcement. Countermeasures against overflow. Countermeasures against denial of service. Ver3.9.4 -------------------------------- - Displayed LTE module version of the model below. model: CPS-MCS341G5-DS1-130 Problem Fix - The FacilityView bug-fixed as follows: Communication will be interrupted if it continues to operate for more than 30 days. There is a possibility that blank data may be sent while updating the CONPROSYS firmware. Ver3.9.3 -------------------------------- Problem Fix - After data transmission failure, the default gateway is lost from the routing table. model: CPS-MCS341G5-DS1-130 - Unable to connect to OPC UA during Basic256Sha256 certificate authentication. - Output is not reflected when bit data update request timing overlaps for the same module from multiple Modbus masters. Ver3.9.2 -------------------------------- - The support for the FacilityView function started. modelFCPS-MCS341-DS1-131, CPS-MCS341G5-DS1-130 - SD card write-protect function enabled. - The support for the OPC UA client function of Node-Red started. Problem Fix - Wireless LAN connection does not recover from a slow state when the communication speed slows down. Ver3.9.1 -------------------------------- - Support for requesting DHCP clients with broadcast flag ON/OFF. - Added "Wireless LAN Alive Monitoring" item to the Wireless LAN Settings screen. - The function to set startup data was added to the TAG settings of the tag edit function. Product concerned : CPS-MCS341G5-DS1-130 Problem Fix - Fix the process of restart LTE module. model: CPS-MCS341G5-DS1-130 - In the tag edit function, after saving the initial value, it may not be set at startup. - Email sending function does not resend properly. - VTC "WAIT" component stops when CONPROSYS time is set to a past date. - VTC was updated (ver1.85 to ver1.86). For details, refer to gOnline Helph. Ver3.9.0 -------------------------------- - Added the following vulnerability countermeasures. 1. OS Command Injection Vulnerability In the following page, the entered value is not properly validated, which makes it possible to execute OS commands. [Network] maintenance page [Mail] setting page [Static Routing] setting page [Port Forwarding] setting page [IP Filter] setting page 2. Firmware tampering vulnerability Firmware structure can be analyzed due to insufficient cryptographic strength of firmware update files. 3. Vulnerability to inadequate access restrictions Network maintenance page originally accessible only with administrator privileges can be accessed with normal privileges. Problem Fix - The "Connect" component does not work in the VTC subroutine process. Ver3.8.8 -------------------------------- - Added protocol setting to port forwarding function. Problem Fix - MQTT service stops after disconnecting from server. - For data transmission function, the probability that transmitted data may remain depending on the device settings. - Router function cannot be set due to timing of activation of 3G network. - Deleting a file on the FTP server, but still receiving the previous file. - VTC processing proceeds even though FTP reception has not been completed. - VTC was updated (ver1.82 to ver1.85). For details, refer to gOnline Helph. Ver3.8.7 -------------------------------- - Changed the number of TOPICs for MQTT publish/subscribe to a maximum of 16. - Added "1 min" setting item to Cycle of LTE Alive Monitoring on the LTE setting. - Added "2: SD card error" and "3: write error" for "SD Recognition" in Modbus status. - The functions gForced Rebooth and gRepair SD and Rebooth were added. - The support for the router function started. DHCP server, static routing, port forwarding, and IP filter functions were added. Problem Fix - CHS settings are not reflected when Data Transfer Service is restarted. - In the tag edit function, the "%" character is empty when registered as a STAG. - Modified so that data transmission can continue even if SD is in an error state when "Auto Backup" is enabled in the Data Transfer setting. Ver3.8.6 -------------------------------- Problem Fix - CPS-MCS341Q-DS1-131 bug-fixed as follows: Added a process to restore communication when a communication error occurs in the configuration of a child unit. Ver3.8.5 -------------------------------- - Changed the method for transmitting blank data to Azure. - For the "Auto Backup Folder", when there is no free space on the SD card when creating a new compressed file (YYYYMMDD.tgz), added the process of deleting the oldest compressed file to free up space. - Rebooting function for NTP time synchronization service was added. Problem Fix - When using CPS-COM-1QL, the transmit LED remains lit but stops working. - MQTT tag setting is not initialized by DIP switch. - CPS-MCS341Q-DS1-131 bug-fixed as follows: Review of the channels that can be selected from the 920MHz page of the web setting screen. Corrected to set the carrier sense value and transmit carrier sense time according to the setting parameters. In 920MHz communication, sending a request from a parent to a child is lost. Depending on the setting, time synchronization may not be set. - VTC was updated (ver1.80 to ver1.82). For details, refer to gOnline Helph. Ver3.8.4 -------------------------------- - Added the communication monitoring interval to the 920Mhz configuration screen. Problem Fix - Data hopped in 920MHz communication causes a thumb check error. - 920MHz communication stops. - The first MQTT transmission by VTC does not work. - If the comments in the configuration file are empty characters, the text doesn't disappear after restoring the TAG information. Ver3.8.3 -------------------------------- - Added a function to restart the device when kernel panic occur. - The LED control processing for shutdown by the MCS341 series power switch is integrated with the processing by the MC/MG341 series shutdown switch. - Added Expansion SDK Supports control of serial devices of stack model expansion I/O modules from custom program. Add custom type [file]. Problem Fix - Fix the process of restart 3G module. model: CPS-MCS341G-DS1-130 - Fixed display of COM port number when connecting to CPS-MM-LC. - 920Mhz setting is not reflected in User's Restrictions. - Expansion SDK was fixed Cannot remove or edit options of custom programs for startup if they contain the "/" character. Unable to get local time in custom program. - VTC stops working when VTC accesses an unregistered 920MHz Child unit. Ver3.8.2 -------------------------------- - Changed the method for transmitting Japanese data to Azure. - The function was added to the product 3G model(CPS-MCS341G-DS1-130) and LTE model(CPS-MCS341G5-DS1-130). Added a setting to enter the PIN code if the SIM is locked. Added AT command history on the log page. Problem Fix - Fix CHS function below "Cloudkey" can't be registered when a new tag is added to it. - Parentheses, "(" and ")", can't be used for password on 3G setting. - Fixed startup process of CPS-MCS341G-DS1-130. - Even if the area is read-only, it is possible to read written data from IO space(0x3a2900) soon after writing. - The IO module hangs while blinking on startup. - Remove startup noise of CPS-COM-1QL. - VTC was updated (ver1.79 to ver1.80). Baudrate:460800 bps can be selected from serial setting of "Link setting". For details, refer to gOnline Helph. Ver3.8.1 -------------------------------- - Added the function to reassign the IP address when the IP address of the wired LAN (eth0) is lost. - Changed the restoring function to restore the specified or all items. - The device file that can be used in the expansion SDK custom program was added. Problem Fix - VTC was updated (ver1.78 to ver1.79). For details, refer to gOnline Helph. Ver3.8.0 -------------------------------- - The support for the LTE and SMS functions started (the CPS-MCS341G5-DS1-130 model). - The industrial value conversion function for analog input values was added (the CPS-AI-1608LI and CPS-AI-1608ALI modules). Problem Fix - On the Monitoring page, the CNC display did not appear (CPS-MCS341G-DS1-131). Ver3.7.1 -------------------------------- - The backup function was added. SD card was added as a destination to download the backup file to. The name of the backup file was changed. - SMS function was added to the product 3G model(CPS-MCS341G-DS1-130). - The restoring function was changed to restore the specified items. - Functions for FTP were added. Files are able to be sent and received to and from multiple FTP servers. The prohibited character "." to be used in the middle of a folder name was changed to a permitted character. - The number of characters for a password was increased. (30 to 64 alphanumeric characters) in the [Mail] setting page. - On the [Time] setting page, the function was changed to write the time in temporary storage space and RTC by clicking the gUpdateh button. - The settings of the "Server Connection Timeout" and the "Data Transfer Timeout" were added in the [Data Transfer] function and the[FTP Put] function. - The number of characters for a client ID was increased. (23 to 256 alphanumeric characters) in the [MQTT Connection] page. Problem Fix - Unnecessary DNS queries were sent to the 3G network. - The values of VTC "Batch Read" control and "Batch Read (Str)" control were sometimes unable to be viewed properly. - Setting up the Data Transfer Service generated file names with wrong dates. - VTC was updated (ver1.77 to ver1.78). For details, refer to gOnline Helph. Ver3.7.0 -------------------------------- - For FTP function, made the folder hierarchy settable from VTC. - The setting of NTP synchronization time became available. - The functions in MQTT Client were added. The number of MQTT publish/subscribe data were increased up to 3000 for each cloud key. The support for CSV import/export for the data settings in MQTT publish/subscribe were added. Enable and disable functions for each data in MQTT publish/subscribe were added. Two types for the publishing options in MQTT publish setting were added. Changed for cloud key to be specified when STAG is set for payload in MQTT subscribe setting. Rebooting function for MQTT service was added. - Modbus Slave function The support for the single holding register writing (function code : 0x06) started. AO module (0x0000-) - Modbus area web monitoring function/writing function were added. - The support was added for the extension SDK USB serial device to be controlled by custom program. - HMI was updated (ver2.18.0 to ver2.18.1). For details, refer to "Online Help". - VTC was updated (ver1.76 to ver1.77). For details, refer to "Online Help". Problem Fix - The MQTT bug-fixed as follows: The check process upon uploading the certificate on MQTT connection setting screen. Upon starting up MQTT Client, a connection started to the Broker before time setting has been completed. - OPC UA did not work when using Link local address. - Data were sent in a different format file from the specifications in the data transfer function. - An additional letter was added when selecting [CR+LF] in VTC log control. - The following data were not deleted even when they were kept longer than three days. Send Folder (Azure) Send Folder (Mail) Send folder(FTP) Send Folder (Task-CHS) Resend Folder (Azure) Resend Folder (Mail) Resend folder(FTP) Resend Folder (Task-CHS) - Blank data were occasionally sent. Data Transfer Service VTC cloud transmission Ver3.6.1 -------------------------------- Problem Fix - Some problems with LED control LED(ST1)flashes when turning on the power. LED(PWR, ST1)flashes when restoring the factory settings. Ver3.6.0 -------------------------------- - MQTT Client function was added. - Specifying and function for destination service were added in data transfer settings. - New support for wireless LAN USB was available. - HMI was updated (ver2.17.1 to ver2.18.0) For details, refer to gOnline Helph. - VTC was updated (ver1.72 to ver1.76) For details, refer to ongOnline Helph. Problem Fix - List cannot be displayed on Tag edit screen when accessing from IE11 Ver3.5.2 -------------------------------- - Displaying a warning popup was added when the pre-set user password is remained as the default settings. - The number of characters that can be entered in the option of the ROMSDK custom program edit screen (16 characters to 100 characters) was increased. - Help for TAG editing was added. - HMI was updated.(ver2.17.0 to ver2.17.1) For details, refer to gOnline Helph. - VTC was updated.(ver1.70 to ver1.72) For details, refer to gOnline Helph. Problem Fix - For Azure transmission, the files are divided to send if the file size is 1023 bytes or greater. - CPS-MM-LC The default value was changed. Ver3.5.1 -------------------------------- - Service Restart supports. Data Transfer, PLC, 3G, 920MHz, OPCUA - Added OPC UA functions. The Listen port is able to be edited. The Response Address is able to be edited. The Anonymous Connection is able to be valid or invalid. - HMI update (ver2.16.8¨ver2.17.0) Refer to Online Help for details. - VTC update (ver1.61¨ver1.70) Refer to Online Help for details. Problem Fixs - TAG Edit 4 byte characters were not able to be changed in Binary value. The pop-up for help was not displayed correctly sometimes. - Setting value more than 128 words was not displayed WEB setting. - User/Password setting If User Name has only number, it can't be deleted. - Setting Range for FTP setting is changed. FTP host name (address), User - Irregular stop happened to 920MHz communication. - CPS-MM-LC The setting page was changed. It kept previous value when CPS-MM-LC power is off. - CPS-AI-1608ALI,CPS-AI-1608ALI Analog input value was captured from off-by-one channel in specific envir environment. - CPS-A0-1604LI, CPS-AO-1604VLI It didn't work properly. Ver3.4.2 -------------------------------- Problem Fix - Setting range of the setting below was changed. Wireless LAN: Encryption Key WPA ... 8-63 alphanumeric characters and symbols except space( ), linefeed(CR+LF),double quotation mark("),single quotation mark('), backslash(\) and backquote(`), or 64-digit hexadecimal number - Write request(Coil 0x05) to DIO with MODUBS protocol didn't work properly. - Expansion SDK was fixed Custom program was not excuted in the boot process Custom program was not saved to SD Ver3.4.1 -------------------------------- Problem Fix - if aploaded a file which has space in name in HMI, ROM remaining capacity was not correctly checked. - ROM remaining capacity was increased by changing file structure. - Communication and settings did not work properly with half-duplex CPS-COM-*PD. - VTC update (ver1.60¨ver1.61) Refer to Online Help for details. Ver3.4.0 -------------------------------- - Added Expansion SDK Refer to 'Reference Manual:CONPROSYS Expansion SDK' for details. - VTC update (ver1.42¨ver1.60) Refer to Online Help for details. Problem Fix - The DIO settings of DIO module is automatically changed. Ver3.3.1a -------------------------------- Problem Fix - CPU module DIO doesn't work properly as user's settings. Ver3.3.1 -------------------------------- - Added TAG Edit function TAG information import/export - HMI update (ver2.16.2¨ver2.16.8) Refer to Online Help for details. - VTC update (ver1.41¨ver1.42) Refer to Online Help for details. Problem Fix - Some MTConnect settings from Web browser were unable to be done. - Modbus status information: Timer (100ms) in specialized functions was unable to operate properly. - In 3G setting, the probability that the product freezes when the 3G alive monitoring is enabled. Product concerned : CPS-MCS341G-DS1-130 - The DIO settings of DIO module is automatically changed. Ver3.3.0 -------------------------------- - Added the VTC functions in CONPROSYS series The number of task pages to be saved is increased. Tasks in up to 20 pages are able to be edited, saved, and debugged. Increased TAG and STAG functions TAG and STAG variables are increased up to 500. The following functions are added. Comment setting Display function Monitoring function Comment display function is added in HMI and VTC. The operation status graph is added in HMI graph item. -Increased the user management function Limitations on the functions for a general user are changed.(Administrator only) - Wireless LAN encryption support (NONE,WEP,WPA-PSK(AES),WPA-PSK(TKIP),WPA2-PSK(AES),WPA2-PSK(TKIP),WPA/WPA2-PSK(AUTO)) - Modified to update the RTC time after the completion of NTP time synchronization. - CPS-MCS341G-DS1-130 supports OPC UA/MTConnect Problem Fix - The probability that WEB setting screen was not displayed properly when using Internet Explorer. - The probability that the wireless LAN was not linked properly. - On mail setting page, multiple registration of mail address by separating with comma was unable to be done. Ver3.2.1 -------------------------------- Problem Fix - Abnormal value is input in I0R, when measured data of I0/I0R of CPS-MM-LC is fetched from TASK - Modified to check ROM capacity when settings are saved and firmware is updated. - The file will be remained in the Send Folder, when several "Send Azure IoT" were excuted at the same time. - The problem which the files remain in "Send Folder(Azure)" when more than 2 process of "Send Azure IoT" on VTC are excuted at the same time. - Storage life for resend file (2 days -> 3 days) - There is a possiblity for meadured data is deleted from the resend file(.csv). Folder: Send Folder (Data Transfer Service) Send Folder (Task) Send folder(Child unit) Send Folder (PLC) Resend Folder (Data Transfer Service) Resend Folder (Task) Resend folder(Child unit) Resend Folder (PLC) Ver3.2.0 -------------------------------- - Support I/O Module CPS-MM-LC (Leakage Current Monitoring Module) - Setting page for the module was added. - The tag (I0/I0r/Va/R), which get the data from the module, was added to HMI. Problem Fix: - A measures was added for preventing the network problem happening. - The problem whichgDiag.pagehcan not be opened was fixed Model:CPS-MCS341Q-DS1-131,CPS-MCS341-DS1-131 - The Conversion accuracy of analog output has over 15LSB when the controller connected CPS-AO-1604LI or CPS-AO-1604VLI. Ver3.1.0 -------------------------------- - WEB setting screen: Display of address in Modbus is unified in hex. Problem Fix: - When specific string was in STAG, it was unable to be displayed on HMI. - Tasks became unstable when using variables in VTC operation. - The gOpen from local diskhin HMI&VTC was unable to operate in Firefox 61 or later versions. - Modified the following settings on WEB setting screen Setting range: Domain name to Domain name[0 to 128 of one-byte alphanumeric letters, hyphen (-), and dot (.)] 3G: APN Time: NTP server FTP: FTP host name Mail: SMTP server Ver3.0.2 -------------------------------- - Top page will be shown properly if move to the old page for Ver.2XX. - The setting page refers to a browser setting for langugage. - Change the process of extracting file. Problem fix: - Devices can not be set and communicate with FANUC CNC(CPS-MCS341-DS1-131,CPS-MCS341Q-DS1-131) - Error code(0x40) will be indicated due to the lack of resource queues when the write procecss happens form a device to CONPROSYS via F•eIT protocol. - BuiltInPowerState of Modbus status(0x5023) is not updated based on the setting. - There is a possibility which the device accidentally excute restart and shutdown depend on the IE setting. Ver3.0.1 -------------------------------- Problem fix: - Compressed file(.tgz) is not shown from Auto Backcup Folder. - NTP result are not correctly stored in Modbus address(0x5000~) after synchronization with NTP server. - Updated Help and Setting Range of WEB setting screen. Ver3.0.0 -------------------------------- - VTC update (ver1.21¨ver1.30) -Calculating control was added. -For system information control, the contents such as serial number were added. - HMI update (version 2.12 to 2.14) -Refer to Online Help for details. - Upgrade WEB setting screen -920Mhz sampling data transfer and reception function was added. -Support communication with the wireless I/O module of 920Mhz model (DIO-0404LY-WQ,AI-1004LY-WQ). Problem fix: - The system shuts down when using TP link driver (8188eu). -Updating stops when connecting through wireless LAN - String calculation control of VTC worked differently from the previous version. Fixed: Insert an empty string into STAG when number of characters to extract is beyond the specified scope or 0. - Send file and Resend file were not sent properly from VTC upon FTP sending. Ver2.8.0 -------------------------------- - VTC's Vup ver1.11¨ver1.21 - "String treats as" property was added in each control of Calc String and Split String. - "Get data size" was added in Action property of Str2Num control. - FTP(Put) and FTP(Get) controls were added. - FANUC CNC input control was added. - The contents of system information control were modified. Problem fix: - When reading a file, modify to delete gCRh, gLFh or gCRLFh if the gCRh, the gLFh or the gCRLFh is found at the end of the string. - FTP client function was added. - The group which has the intermediate privilege between the root and the other was added. (The group name: User) - The group names were redefined due to an addition of the user group. Root- Admin User- User (intermediate group) Other- Guest Problem fix: - In the system information register (Modbus0x5014), the last letter of "TransferErrorInfo" cannot be written. - The second time Open fails when the VTC commands the COM port to be opened or closed. - FANUC CNC data cannot be set in PrintOutput in the specified order. - The selected OPC UA client certificate cannot be deleted on OPC UA setting page. - On the file display page, data file in the folder of Azure and Mail cannot be deleted. - In Task, when the [Input String] control is placed after the [Connect] control is placed, a message is obtained that was received while the [Disconnect] control is being placed or before the [Connect] control is placed. Ver2.7.0 -------------------------------- - The function was added in OPC UA containing model(CPS-MCS341-DS1-131,CPS-MCS341Q-DS1-131). - STAG was added in UA tree. - Support MTConnect(CPS-MCS341-DS1-131,CPS-MCS341Q-DS1-131j - MTConnect was added in the menu of configuration. - MTConnect was added in the service setting of configuration page. - Change the file at the initial setting of the monitoring screen. - Problem fix: Task closed unexpectedly when device ID, channel, bits were specified for the property values of VTC task items (input and output) to run. Ver2.6.2 -------------------------------- Problem fix: - VTC cannot read/write data from/into certain configurable devices. - Authentication type of SIM card cannot be set properly. - Available memory of HMI cannot be shown correctly. Ver2.6.1 -------------------------------- Problem fix: When connecting to the network via USB wireless LAN, timeout will be performed if IP address is not assigned from dhcp server within a specified time. Problem fix: Even SW1 No. 2 is on, USB wireless LAN operates by user setting. - A box becomes inactive if Search is selected in SSID of the wireless LAN set ting.The scan button and the list become inactive if Manual is selected. - TCP port (1~65535) can be set on OPC UA setting page. - The notation of OPC-UA changed to OPC UA. Ver2.6.0 -------------------------------- - Administrator setting function was added. Separate into two groups of Administrator (root) and General users (other) - The additional function in Login password setting was added. A user can choose whether to enter User and Password is necessary at log-in. (User and Password are always required in the Administrator page) - HMI Editor Version upgrading ver2.12.1 - Task Editor Version upgrading ver1.11 - TAG00 - 99 were added in the OPC-UA tree. - Azure data sending function became available. - File compression function in Auto backup folder was added. Backup files are compressed at 3:59 am once a day. (excludes from 0:00 to 3:59) - Support communication with FANUC CNC (Model 931 exclusively) Serial communication port setting in the device setting was added on the Web configuration page. Communication data was added in OPC-UA data. - Start-up process of the DIP switch changed. When DIP-SW1 is 2:ON 3:OFF, IP starts with default state. (login user should not be default state) - TELEC number display was added in the system information of 3G model. - Mail sending function was added. - USB Wifi support - Updated Kernel - Enhanced Modbus Slave function System information was added to 0x5000 and later addresses of the input register - Check the ROM space when saving HMI settings Ver2.4.0 -------------------------------- Apply CDS2 -Added "CDS2 format" and "Cloudkey" for Data transfer setting. When CDS2 was set as gEnableh, a format of csv file sent by data transfer service was changed as follows: -Cloudkey -Date -Time -Millisecond After the above, measured data were listed. -Added "Datetime(CDS)" for VTC log control. -Added a name "Second" for a file that was sent to Cloud server from VTC. File name: YYYYMMDDhhmmss_filexx.csv Apply Proxy - Added Proxy setting for the network setting Ver2.3.0 -------------------------------- - CPS-MCS341Q-DS1-130 support - Problem fix: When a task created in VTC accesses I/O modules, the assignment of task stops. The modulesFAll modules except serial communication modules. (If the device tree is not used, the problem does not occur). Ver2.2.0 -------------------------------- - I/O module applied - CPS-DI-16L - CPS-DI-16RL - CPS-DO-16L - CPS-DO-16RL - Problem fix:Communication with LAN port did not operate. Unable to update from version 1.0.0 to the latest Ver2.1.1 -------------------------------- - Problem fix: Data transmission to Cloud server did not work properly when operating with the screen display of HMI, VTC for a long time. - VTC fix: - String calculation with a control cord did not perform properly. - When obtaining a length of the string, -1 was returned if a control code was included. - When performing string comparison, true was always returned if the length of the string was 0. - When performing comparison, true was returned if some part of the string was matched. - During debugging, the contents could not be read efficiently when the TAG number was changed. - To support counter value, the logic operation was changed from int to unsigned long. Ver2.1.0 -------------------------------- -CPS-MCS341G-DS1-130 support Ver2.0.0 -------------------------------- -I/O module applied -CPS-AI-1608ALI -CPS-AO-1604VLI -CPS-DIO-0808RL -CPS-RRY-4PCC -CPS-CNT-3202I -Implement new monitoring and task -Module setting monitor was added. -Device list of system information was deleted Ver1.0.2 -------------------------------- -Problem fix: AO of CPS-AO-1604LI did not function properly. -I/O module driver was upgraded. Ver1.0.1 -------------------------------- -I/O module applied -CPS-AI-1608LI -CPS-AO-1604LI -CPS-SSI-4P -Task programming functions were added. The functions Cloud server transmission File generation File read File operation Log file output SD card backup Items Cloud,File,Read,Log,Flog Menu File -Auto backup function for transmitting data to cloud server was added. Enable/Disable could be switched on Data transfer setting. The backup files were set to the SD card. -Web monitor function was added. File view File browsing/deleting -Transmission waiting folder The list of files to be sent to a cloud server. Retention periodFDeleted after three days passed or upon rebooting. -Re-transmission waiting folder The list of files to be re-sent to a cloud server. Retention periodFDeleted after three days passed or upon rebooting. -Task SD card folder The list of SD card files generated by task programming. Retention periodFNo limitation -Task RAM folder The list of RAM files generated by task programming. Retention periodFDeleted upon rebooting. -Task SD backup folder The list of backup file generated by task programming. Retention periodFDeleted after 365 days passed. -Auto backup folder The list of file generated by auto backup function of sent data to cloud server. Retention periodFDeleted after 365 days passed. Time synchronization setting. Date and time setting. Write date and time into hardware. Network setting Network continuity check. Unit id setting Data transmission setting Transmission intervalFone minute -Problem fix: Web monitor setting was instantly reflected. Modified -Synchronization server of time synchronization setting. -Data destination URL to which data was sent -The written word on the Web monitor was modified. Modified "modbus" ¨ "Modbus" -Modified start-up process Start up the service with the time of hardware when time synchronization could not be carried out. -LED flashing interval was adjusted. Ver1.0.0 -------------------------------- Released the first edition. -CPS-MCS341-DS1-111 -I/O module applied -CPS-DIO-0808L -CPS-DIO-0808BL -CPS-COM-1PC -CPS-COM-2PC -CPS-COM-1PD -CPS-COM-2PD