===================================================================== = CPS-MC341 Series Firmware Upgrade = = CPS-MC341 Series firmware Ver2.5.1 = = CONTEC Co.,Ltd. = ===================================================================== Ÿ Table of Contents ======= Introduction Before upgrading Version upgrading procedure Version upgrading history Ÿ Introduction =========== Thank you for your continued patronage of CONTEC products. This describes the additional information of CPS-MC341 series firmware upgrade. For how to use the product, please visit our website and see the system setup guide. (http://www.contec.com) Ÿ Firmware upgrading precaution =========== *Do not downgrade the firmware. *The required time for upgrading CPS-MC341-ADSC1-931: about 15 minutes other models: about 40 minutes *********************************************************************** * Do not turn off the power when LED ST1 and ST2 are on. * * Doing so may break the data and device will be unable to boot. * *********************************************************************** * The former task program (1.8.1 or earlier) will convert and run in the .2.0.0 and later version. However, the screen that was created in the former monitoring (1.8.1 or earlier) cannot be used. The screen needs to be created again with new tools. Ÿ Before upgrading =========== Have the followings ready EProduct (CPS-MC341 series) EHost computer ELAN cable EFirmware upgrade file Ÿ Version upgrading procedure =========== 1.Turn on the power of the CPS-MG341 product. 2.Connect the product to a host computer with a LAN cable. 3.Access the product via web browser from the computer . If the CPS-MG341 still has the default setting, set the host computer on the same network (e.g.:10.1.1.102) and enter "http://10.1.1.101 " in URL. If you are uncertain of your IP address, the default settings (10.1.1.101) can be restored temporarily by turning on the power with SW1-2 switch on. 4.Log in the product. You will be asked to enter a user name and a password. Enter them and click "OK" button. If you are uncertain of the user name and/or password, the default settings (User nameFmc341, PasswordFmc341) can be restored temporarily by turning on the power with SW1-2 switch on. 5.Follow the instruction below to go to "Firmware version up" menu. In the "Status nemu", click "Maintenace menu", and then "Firmware version up"in the Backup group. 6.Upload the firmware upgrade file. Click "Browse" button. Specifiy the file in the host computer to upload. Click "upload" button. *If the firmware upgrade file is compressed (extension:zip), decompress it before uploadingiextension:bin). 7.Upgrading will start and the product will be rebooted. LED display changes as described below. Upgrading ‡@PWR on, ST1 flashing (slow), ST2 off ‡APWR on, ST1, ST2 flashing (fast) ‡BPWR on, ST1, ST2 off ‡CPWR on, ST1, ST2 flashing (slow) Rebooting ‡DPWR, ST1, ST2 on ‡EPWR on, ST1, ST2 off ‡FPWR on, ST1 flashing (slow), ST2 off 8.After rebooting completes, check the version. Access the product via web browser again. From "Maintenance menu", click "System information" under the group of System. Ÿ Version upgrading history =========== Ver2.5.1 -------------------------------- Problem Fix - When writing with F•eIT protocol into a device, it shoultid response by 0x40 if the resource of queue was insufficient. Ver2.5.0 -------------------------------- - VTC's Vup ver1.11¨ver1.21 - "String treats as" property was added in each control of Calc String and Split String. - "Get data size" was added in Action property of Str2Num control. - FTP(Put) and FTP(Get) controls were added. - FANUC CNC input control was added. - The contents of system information control were modified. Problem fix: - When reading a file, modify to delete gCRh, gLFh or gCRLFh if the gCRh, the gLFh or the gCRLFh is found at the end of the string. - FTP client function was added. - The group which has the intermediate privilege between the root and the other was added. (The group name: User) - The group names were redefined due to an addition of the user group. Root- Admin User- User (intermediate group) Other- Guest Problem fix: - In the system information register (Modbus0x5014), the last letter of "TransferErrorInfo" cannot be written. - The second time Open fails when the VTC commands the COM port to be opened or closed. - FANUC CNC data cannot be set in PrintOutput in the specified order. - The selected OPC UA client certificate cannot be deleted on OPC UA setting page. - On the file display page, data file in the folder of Azure and Mail cannot be deleted. - In Task, when the [Input String] control is placed after the [Connect] control is placed, a message is obtained that was received while the [Disconnect] control is being placed or before the [Connect] control is placed. Ver2.4.2 -------------------------------- - Problem fix: Failed to obtain IP address of 3G-wired connection in the global 3G model (CPS-MC341G-ADSC1-110). - Problem fix: Specifying Adapter of 3G-wired connection was incorrect. - Problem fix: Wireless LAN was not automatically connected to AP. Ver2.4.0 -------------------------------- - The function was added in OPC UA containing model(CPS-MC341-ADSC1-931) - STAG was added in OPC UA tree. - Support MTConnect(CPS-MC341-ADSC1-931j - MTConnect was added in the menu of configuration. - MTConnect was added in the service setting of configuration page. - Change the file at the initial setting of the monitoring screen. - Problem fix: SIM card authentication type was not set properly. - When saving the monitoring screen, ROM remaining capacity was displayed smaller than it actually was. Ver2.3.3 -------------------------------- - Problem fix: Task closed unexpectedly when device ID, channel, bits were specified for the property values of VTC task items (input and output) to run. Ver2.3.2 -------------------------------- Problem fix: When connecting to the network via USB wireless LAN, timeout will be performed if IP address is not assigned from dhcp server within a specified time. Problem fix: Even SW1 No. 2 is on, USB wireless LAN operates by user setting. - A box becomes inactive if Search is selected in SSID of the wireless LAN set ting.The scan button and the list become inactive if Manual is selected. - TCP port (1~65535) can be set on OPC UA setting page. - The notation of OPC-UA changed to OPC UA. Ver2.3.1 -------------------------------- Problem fix: Task ends when accessing DO from the task. Ver2.3.0 -------------------------------- - Administrator setting function was added. Separate into two groups of Administrator (root) and General users (other) - The additional function in Login password setting was added. A user can choose whether to enter User and Password is necessary at log-in. (User and Password are always required in the Administrator page) - HMI Editor Version upgrading ver2.12.1 - Task Editor Version upgrading ver1.11 - TAG00 - 99 were added in the OPC-UA tree. - Azure data sending function became available. - File compression function in Auto backup folder was added. Backup files are compressed at 3:59 am once a day. (excludes from 0:00 to 3:59) - Support communication with FANUC CNC (Model 931 exclusively) Serial communication port setting in the device setting was added on the Web configuration page. Communication data was added in OPC-UA data. - Start-up process of the DIP switch changed. When DIP-SW1 is 2:ON 3:OFF, IP starts with default state. (login user should not be default state) - TELEC number display was added in the system information of 3G model. - Mail sending function was added. - USB Wifi support - Updated Kernel - Enhanced Modbus Slave function System information was added to 0x5000 and later addresses of the input register - Check the ROM space when saving HMI settings Ver2.2.0 -------------------------------- Apply CDS2 -Added "CDS2 format" and "Cloudkey" for Data transfer setting. When CDS2 was set as "Enable", a format of csv file sent by data transfer service was changed as follows: -Cloudkey -Date -Time -Millisecond After the above, measured data were listed -Added "Datetime(CDS)" for VTC log control. -Added a name "Second" for a file that was sent to Cloud server from VTC. File name: YYYYMMDDhhmmss_filexx.csv Apply Proxy - Added Proxy setting for the network setting Ver2.1.5 -------------------------------- ModelFCPS-MC341-ADSC1-931 -Supported communication with FANUC CNC. -Added the serial communication signal in device setting. Ver2.1.4 -------------------------------- Problem fix: Unable to update from the version earlier than Ver.1.4.0 to the latest version. ModelFCPS-MC341Q-ADSC1-111 -Enhanced the check function for 920MHz communication data. -Optimized the 920 MHz communication process. -Set the maximum number of resending files from Slaves to Master by 920 MHz communication to five. Ver2.1.3 -------------------------------- -Problem fix: Read a value different from the set value when reading TAG information. Ver2.1.2 -------------------------------- ModelFCPS-MC341Q-ADSC1-111 -Enhanced the check function for 920MHz communication data. Ver2.1.1 -------------------------------- ModelFCPS-MC341Q-ADSC1-111 -Problem fix:Data was damaged when sending data from Slaves to Master by 920 MHz communication. Necessity to enable the service to send the collected data from Master to cloud server. Master was likely to end abnormally. -Data store folders were added. -"Send" folder (Slave) -"Resend" folder (Slave) Ver2.1.0 -------------------------------- -The CPS-MC341-ADSC1-931 model was added. - Data transmission to the cloud server did not operate properly when running for a long time with the screen of HMI, VTC displayed. -Problem fix: Troubles occurred when using a relay service to connect with cloud server. ModelFCPS-MC341G-ADSC1-111, CPS-MC341G-ADSC1-110 -TELEC number display was added to the system information screen. Ver2.0.3 -------------------------------- -Monitoring -Added the images of Switch and Lamp controls. Changed the default image. -Changed the wait-time of timeout longer while data was saving to ROM from monitoring or tasks. -Other: fixed bugs of monitoring. Ver2.0.2 -------------------------------- -Problem fix: Unable to send data from tasks to cloud server. Models CPS-MC341G-ADSC1-111 CPS-MC341G-ADCS1-110 CPS-MC341Q-ADSC1-111 Ver2.0.1 -------------------------------- -Problem fix: Data could not be sent to cloud server. Applied version 2.0.0 Applied products CPS-MC341G-ADSC1-111 CPS-MC341G-ADCS1-110 CPS-MC341Q-ADSC1-111 -Problem fix: Monitoring task did not work properly when a backup file was Ver2.0.0 or older. -Improved a monitoring perfomance. -Problem fix: Chinese version could not viewed in a certain monitor. -Problem fix: A few monitoring issues, task bug Ver2.0.0 -------------------------------- -Implement new monitoring and task -CPS-MC341-ADSC1-911F1 applied -CPS-MC341-ADSC1-911F2 applied -CPS-MC341-DS11-111 applied -Applied Chinese version Ver1.8.0 -------------------------------- -CPS-MC341G-ADSC1-110 -Modified MAC address of 3G model. -Modified menu display -Modified the display upon selecting DHCP of network setting. -Problem fix: LED ST2 did not light up when data transer failed under a certain condition. Ver1.7.2 -------------------------------- -CPS-MC341G-ADSC1-111 exclusively Problem fix: Could not recover from 3G-wired disconnection. Ver1.7.1 -------------------------------- -Task programming functions were added. The function Cloud server transmission File generation File read File operation Log file output SD card backup Items Cloud,File,Read,Log,Flog Menu File -Auto backup function for transmitting data to cloud server was added. Enable/Disable could be switched on Data transfer setting. The backup files were set to the SD card. -Web monitor function was added. File view File browsing/deleting -Transmission waiting folder The list of files to be sent to cloud server. Retention periodFDeleted after three days passed or upon rebooting. -Re-transimission waiting folder The list of files to be re-sent to cloud server. Retention periodFDeleted after three days passed or upon rebooting. -Task SD card folder The list of SD card files generated by task programming. Retention periodFNo limitation -Task RAM folder The list of RAM files generated by task programming. Retention periodFDeleted upon rebooting. -Task SD backup folder The list of backup file generated by task programming. Retention periodFDeleted after 365 days passed. -Auto backup folder The list of file generated by auto backup function of sent data to cloud server. Retention periodFDeleted after 365 days passed. -Problem fix: Web nonitoring setting was instantly reflected. Modified -Synchronization server of time synchronization setting. -Data destination URL to which data was sent. Ver1.7.0 -------------------------------- -CPS-MC341-DS2-911 -Web monitor functions were added.(CPS-MC341-DS2-911 exclusively.) Time synchronization setting. Date and time setting. Write date and time into hardware. -Web monitor function was added. Network setting Network continuity check. -Modified start-up process(CPS-MC341-DS2-911 exclusively). Start up the service with the time of hardware when time synchronization cound not be carried out. -920MHz communication stabillized. Ver1.6.1 -------------------------------- -CPS-MC341G-ADSC1-111 -Problem fix: 3G network was disconnected when there was no responses from the server. -Problem fix: Wired network setting was reset when there was no responses from the server. Ver1.6.0 -------------------------------- -CPS-MC341-DS2-111 -Web monitor setting items were added. Unit id in network setting. -Optimize start-up process. Ver1.5.0 -------------------------------- -CPS-MC341Q-ADSC1-111 -Web monitor pages were added.(CPS-MC341Q-ADSC1-111 exclusively) 920MHz communication setting. 920MHz slave setting. 920MHz hop setting. 920MHz The list of accessible divices. 920MHz the list of device conditions. Ver1.4.0 -------------------------------- -CPS-MC341-A1-111 -Display on Web monitor was modified. Modbus Ver1.3.1 -------------------------------- -The functions used in cloud collaboration were added. ID display. -Modified Modbus format. The field length of response -Display on Web monitor was modified. For each item of network setting. Ver1.3.0 -------------------------------- -CPS-MC341G-ADSC1-111 -Display on Web monitor was modified. User setting monitor. Ver1.2.0 -------------------------------- -CPS-MC341-DS1-111 -Display on Web monitor was modified. Mainitenance menu.ya -Restore of task editting. Problem fix: Restoring number nine and bigger could not be selected. Ver1.1.1 -------------------------------- -Time-zone setting was not reflected in certain functions . -Review start-up process. Start sending data to the server upon completeion of time synchronization. -Problem fix: Obtaining IP address failed a few times. -Problem fix: Input field became inactivated when selecting fixed-IP. Ver1.1.0 -------------------------------- -CPS-MC341-ADSC2-111 -OS modified. Ver1.0.0 -------------------------------- Released the first edition. -CPS-MC341-ADSC1-111